1、洛阳理工学院毕业设计(论文)纺织厂10kv供配电设计摘 要 随着工厂自动化程度的提高,合理的工厂供电系统变得越来越重要,不仅可以保证工厂的正常生产,还能大大的节约电能降低产品的成本,提高生产效率。 本设计为纺织厂供配电系统设计,主要包括电力负荷计算、变电站主接线的设计、电源进线及工厂高压配电线路的设计、短路计算、高低压电气设备选择以及变电站继电保护规划设计和防雷与接地。 同时在设计中采用并联电容器的方法来补偿无功功率,以减少供电系统的电能损耗和电压损失,同时提高了供电电压的质量。从而使整个供电系统更具有其可靠性和灵活性。关键词:电源进线 短路计算 电气设备选择 继电保护 10kV Power
2、Distribution Design of Textile FactoryABSTRACT With the development of factory automation,power supply system becomes more and more important. It not only can guarantee normal production of the factory ,but also reduce the cost of the products, save the electrical energy and increase productivity. T
3、he paper is about the design of the supply and distribution system of a textile factory .It mainly includes the load calculation, the design of substation bus, the design of the inlet line and the high voltage distribution line, short circuit calculation, high and low voltage electrical equipment se
4、lection, the layout of the relay protection and the design of the lightning-protection and grounding.At the same time the design uses shunt capacitor to compensation reactive power to decrease energy losses and voltage losses in the power supply system.It can also improve the quality of the power su
5、pply voltage. So the whole design of the power supply system becomes more reliability and flexibility.KEY WORDS: power system,short circuit calculation,electrical equipment,relay protection2目录前言1第1章 负荷计算31.1 电力负荷计算的内容31.2 电力负荷的表达式31.2.1 年最大负荷31.2.2 平均消耗的功率31.2.3 负荷系数41.2.4 单个三相用电设备组的计算负荷41.2.5 多组用电设
6、备计算负荷的确定51.3 负荷计算61.4 变电所变压器的选择12第2章 无功补偿142.1无功补偿方案设计142.1.1提高功率因数的意义142.1.2补偿装置的确定142.2无功补偿容量计算15第3章 变电站主接线的设计173.1 主接线的基本要求173.2 主接线的选择173.2.1 单母线接线方式173.2.2 单母线分段18第4章 电源进线及工厂高压配电线路的设计194.1 变电所进出线及与邻近单位联络线的选择194.1.1 10kV高压进线的选择校验194.1.2 由高压配电室至主变的一段引入电缆的选择校验194.1.3 作为备用电源的高压联络线的选择校验204.2 0.4kV低压
7、出线的选择21第5章 短路计算225.1 短路电流计算的目的225.2 短路电流计算的方法225.2.1 短路计算235.2.2 计算短路电路中各元件的电抗标幺值235.2.3 K-1点短路计算245.2.4 K-2点短路计算245.2.5 K-3点短路计算255.2.6 K-4点短路计算255.2.7 K-5点短路计算265.2.8 K-6点短路计算26第6章 高低压电气设备选择286.1 一次设备选择与校验的条件和项目286.2 按正常工作条件选择286.3 短路条件校验286.3.1 隔离开关、负荷开关和断路器的短路稳定度校验286.3.2 电流互感器的短路稳定度校验306.4 熔断器和
8、熔体的选择校验316.5 高压互感器的选择与校验326.6 0.4kV侧一次设备的选择336.6.1 NO.1 车间变电所336.6.2 N0.2 车间变电所336.6.3 N0.3 车间变电所346.6.4 N0.4 车间变电所346.6.5 N0.5 车间变电所34第7章 防雷与接地设计367.1 变电所的防雷保护367.1.1 直击雷防护367.1.2 雷电侵入波的防护367.2 变电所公共接地装置的设计367.2.1 接地电阻的要求377.2.2 接地装置的设计37结论38谢 辞39参考文献40附录41附 录 1电气总接线图41附 录 2纺织厂原始资料42外文资料翻译43前言本设计为电
9、气工程及其自动化专业的毕业设计,以供电技术为主线,综合考查学生对本专业各科知识的掌握程度,培养对本专业各科知识进行综合运用的能力,同时也检验了本专业学习四年以来的成果。1. 工厂供电的意义和要求工厂供电,就是指工厂所需电能的供应和分配。除某些特殊的大型工业企业带有自备发电站以外,工厂都是由电力系统的终端降压变配电所,即总降(配)变电所提供电能。总降(配)变电所、供电线路和用电设备构成了一个完整的工厂供电系统。供电系统一旦确定,就决定了用户内部用电负荷的供电可靠性和供电质量。电能易于转换,易于传输,分配简单经济,便于调节、控制和测量等特点,使得电能成为了工业生产的主要能源。能否保证供电的可靠性和
10、电能质量直接影响到工业生产能否正常进行,能否做到合理用电、节约用电、高质量用电成为决定工厂生产力和企业效益的重要因素。因此,设计符合工厂具体负荷情况的供电系统是工业生产的必备条件。做好工厂供电工作对发展工业生产,实现工业现代化,具有十分重要的意义。工厂企业是国家电力的主要用户,完善工厂供电系统的配置对节约能源、支援国家经济建设也有很大的促进作用。为了使工厂供电工作能够切实为工业生产服务,要求做到以下几点:(1) 安全 在电能的供应、分配和使用过程中,不应发生人身事故和设备事故。(2) 可靠 不同级别的负荷对供电可靠性的要求不同,工厂供电系统必须满足相应负荷的要求。(3) 优质 供电系统提供的电
11、能应该满足电力用户对电压、频率等电能质量的要求。(4) 经济 在保证供电可靠性的情况下,供电系统的投资要尽量少,运行费用要尽量低,并尽可能的节约电能和减少有色金属的消耗量。2. 工厂供电设计的一般原则工厂供电设计必须以设计任务书为依据,以国家经济建设的方针、政策、技术规定、标准为准绳,结合工程的实际情况进行。按照国家标准GB50052-95供配电系统设计规范、GB50053-9410kv及以下设计规范、GV50054-95低压配电设计规范、全国通用建筑标准设计.电气装置标准图集等的规定,进行工厂供电设计必须遵循以下原则:(1)遵守规程、执行政策;必须遵守国家有关规定及标准,执行国家有关方针和政
12、策,包括 节约能源,节约有色金属等技术经济政策。(2)安全可靠、先进合理;应做到保障人身和设备的安全,供电可靠,电能质量合格,技术先进和经济合理,采用效率高、能耗低和性能先进的电气产品。(3)近期为主、考虑发展应根据工作特点、规模和发展规划,正确处理近期建设与远期发展的关系,做到远近结合,适当考虑扩建的可能性。(4)全局出发、统筹兼顾按负荷性质、用电容量、工程特点和地区供电条件,综合考虑,确定合理的设计方案。3. 设计的内容及步骤工厂供电系统的设计是根据电力用户所处地理环境、生产工艺对负荷的要求、各个车间的负荷数量和性质、负荷布局以及地区供电条件进行的。要求设计成果能应用于生产实际,能够让该供
13、电系统安全、可靠、经济的分配电能,满足工业生产的需要。设计的具体步骤如下: (1)按照厂区用电设备的资料和其他具体情况,计算负荷。(2)根据负荷等级和计算负荷,选定供电电源、电压等级和供电方式。(3)根据环境和计算负荷,选择变电所的位置、变压器数量和容量。(4)为变配电所选择安全、可靠、灵活、经济的主接线,选择合理的户外高压配电方案。(5)用标幺值进行短路电流的计算。(6)根据短路电流的计算结果,按照正常工作条件、短路时的工作条件、电气设备自身特点进行电气设备的选择和校验,用主接线图表达设计成果。(7)主变压器和馈线电路保护装置的设计及整定,包括保护方式的确认、保护值的整定、保护装置的选择以及
14、灵敏度校验。 (8)变电所的防雷和接地设计,总降的电照设计。(9)需要核算建设所需器材与总投资。 第1章 负荷计算1.1 电力负荷计算的内容 计算负荷又称需要负荷或最大负荷。计算负荷是一个假想的持续性的负荷其热效应与同一时间内实际变动负荷所产生的最大热效应相等。在配电设计中,通常采用30分钟的最大平均负荷作为按发热条件选择电器或导体的依据。 平均负荷为一段时间内用电设备所消耗的电能与该段时间之比。常选用最大负荷班(即有代表性的一昼夜内电能消耗量最多的一个班)的平均负荷,有时也计算年平均负荷。平均负荷用来计算最大负荷和电能消耗量。1.2 电力负荷的表达式 电力负荷根据其对供电可靠性的要求及中断供
15、电在政治、经济上所造成损失或影响的程度,可分为三级:一级负荷、二级负荷、三级负荷。1.2.1 年最大负荷就是全年中负荷最大的工作班内消耗电能最多的半小时平均负荷。年最大负荷利用小时,是假设电力负荷按年最大符合持续运行时,在次时间内电力负荷所好用的电能恰与电力负荷全年实际所耗用的电能相等。按下式计算: (h)(h) (1-1)其中为全年消耗的电量() 有功电量 无功电量1.2.2 平均消耗的功率就是电力负荷在一定时间t内平均消耗的功率,即: (kW) (1-2) 年平均负荷,就是电力负荷全年平均耗用的功率,t取8760(h),即: (1-3)1.2.3 负荷系数最大工作班内,平均负荷与最大负荷之
16、比,称为负荷系数。用、分别表示有功、无功负荷系数,其关系式为: (1-4)1.2.4 单个三相用电设备组的计算负荷需要系数法确定三相用电设备组计算负荷:在供配电系统设计和运行中,常使用需要系数,其定义为: (1-5)式中 用电设备组负荷曲线上最大的有功负荷(); 用电设备组设备容量();其物理意义为: (1-6) 同期系数。负荷系数。线路供电率。 用电设备在实际运行功率时的效率。1。用电设备组有功计算负荷: () (1-7)用电设备的无功计算负荷:(kvar) (1-8)用电设备组的视在计算负荷为:=(kVA) (1-9)用电设备组的计算电流为:(A) (1-10)按二项式发确定三相用电设备组
17、计算负荷.同一工作制单组用电设备有功计算负荷为 无功计算负荷为 (kvar) 式中 b、c为二项式系数,对于不同类型的设备取值不同。1.2.5 多组用电设备计算负荷的确定确定拥有多组设备的干线上或车间变电所低压母线上的计算负荷时,应考虑各组用电设备的最大负荷不同时出现的因数。因此在确定多组用电设备时,应结合具体情况对其有功负荷和无功负荷分别记入一个同期系数和。对车间干线取: 0.850.950.900.97 对低压母线,分两种情况由用电设备组计算负荷直接相加来计算时,取:0.800.900.850.95 由车间干线计算负荷直接相加来计算时,取:0.900.950.930.97 需要系数法确定计
18、算负荷总的有功计算负荷为 (1-11)总的无功计算负荷为 (1-12)则视在计算负荷为 (kVA) (1-13)总的计算电流为 (1-14)工厂的计算负荷,应该是在高压母线上所有高压配电线路计算负荷之和,在乘以一个同时系数。高压配电线路的计算负荷,应该是该线路所供车间变电所低压侧计算负荷,加上变压器的功率损耗,如此逐级计算即可求得供电系统所有元件的计算负荷。但对一般工厂供电系统来说,由于高低压配电线路一般不很长,其损耗较小,因此在确定其计算负荷时往往不计线路损耗。在负荷计算中,电力变压器的功率损耗可按下列简化公式近似计算:有功损耗: 无功损耗: 1.3 负荷计算本设计是为某纺织厂设计一座高压配
19、电所,该纺织厂主要生产化纤产品,大部分车间为三班制,少数车间为两班或一班制。该厂有二级负荷这三级负荷。二级负荷也属于重要负荷,供电变压器可由一台或者两台变压器。当只有一台变压器的时候可采用高压联络线由邻近的单位取得备用电源以满足二级负荷的要求,工厂不致中断供电。只有当负荷较小或者当地供电条件困难时,二级负荷可由一回路10kV及以上的专用架空线路供电。这是考虑架空线发生故障时易于发现且易于检查和修复。当采用电缆线路时,必须采用两根电缆并列供电,每根电缆应能承受全部二级负荷。该纺织厂中锻工车间、纺纱车间、软水站是二级负荷,其余均为三级负荷。工厂负荷计算及无功补偿(1)有功计算负荷: (1-17)
20、(2)无功计算负荷: (1-18) (3)视在功率负荷: (1-19)(4)计算负荷: (1-20)而在NO.1车间里的合计中: (1-21)因为变压器上有功率损耗,所以计算高压配电线路的计算负荷应该是该线路所供车间变电所低压侧计算负荷加上变压器的功率损耗。故:(1) (1-22)(2) (1-23) (3) (1-24) (4)总的计算电流为 (1-25)根据上面公式进行负荷计算有功损耗: 无功损耗: (1-26)NO.1: =821.15NO.2: NO.3: NO.4: NO.5: 高压母线上所有高压配电线路计算负荷之和: =0.77根据计算可得表1-1表1-1工厂负荷统计表车间名称设备
21、容量(kW)需要系数功率因素计算负荷(kW)(kvar)(kVA)(A)NO.1车变锻工车间380.20.651.177.68.89211.692纺纱车间3500.80.80.7528021035制条车间880.80.80.75280210350软水站880.650.80.7557.242.971.5合计826624.8471.792782.921.19损耗11.7446.978高压侧合计826636.8518.79821.1547.71NO.2车变机修车间3000.30.51.7390155.7180仓库400.30.51.731220.7624办公室210.70.61.3314.719.5
22、5124.5合计361116.7196.011228.120.35损耗3.42213.69高压侧合计361120.12212.701244.27714.10NO.3车变织工车间4500.80.80.75360270450染工车间4000.80.80.75320240400食堂400.750.80.753022.537.5合计890710532.5887.51.3513.353.25高压侧合计890723.3585.75930.153.745NO.4车变锅炉房1500.750.80.75112.584.375140.625水泵房1200.750.80.759067.5112.5油泵房300.75
23、0.80.7522.516.87528.125化验区500.750.80.7537.528.12546.875合计350262.5196.875328.1250.54.92216.6875高压侧合计350267.622216.56344.1119.87N0.5车变生活区3000.70.900.48210100.8232.940.353.4913.98高压侧合计213.49114.78242.3913.991.4 变电所变压器的选择1变压器的容量选择:(1)变压器的容量首先要满足在计算负荷下,变压器能够长期可靠运行。对于单台变压器SNTSC,对于两台并列运行的变压器SNT1+SNT2SC,SNT
24、1SC+SC, SNT2SC+SC,式中SC、SC-分别为负荷SC中一级和二级负荷的容量;SNT1、SNT2分别为并列运行的两台变压器的额定容量。(2)为适用工厂发展和调整的需要,变压器容量还应留有一定的裕量。(3)所选方案要满足变压器经济运行的条件。暗备用方式运行时,变压器的容量为70%S50%S,满足条件1、2;其负荷率为50%S/70%S70%,负荷率大于68%,满足条件3。暗备用方式投资省,能耗小,故应用广泛。2变压器调压方式选择 视负荷大小、可靠性要求、电压质量要求而定,一般车间变电所不使用有载调压变压器。3变压器相数的选择 一般选择三相变压器。4变压器台数的选择该工厂引用10kV进
25、线,下分五个车间变电所,每个变电所都可以采用一台或者两台变压器。从技术指标,两台变压器的方案略微优于一台变压器。从经济指标来看,一台变压器的方案远优于两台变压器的方案。所以这里每个车间变电所选一台变压器的方案。5变压器型号的选择根据负荷计算结果表1-1确定各车间变电所变压器型号。NO.1 车间变电所: NO.2 车间变电所: NO.3 车间变电所: NO.4 车间变电所: NO.5 车间变电所: 所选的S9型电力变压器采用无激磁调压,调压范围是5%,足以保证电压质量。表1-2 变压器型号一览表车间变压器型号额定容量(KVA)空载损耗(kW)负载损耗(kW)空载电流(%)阻抗电压(%)联结组标号
26、NO.1 车变10001.7010.300.74.5Yyn0NO.2 车变2500.563.051.24Yyn0NO.3 车变10001.7010.300.74.5Yyn0NO.4 车变4000.804.3014Yyn0NO.5 车变2500.563.051.24Yyn018第2章 无功补偿2.1无功补偿方案设计2.1.1提高功率因数的意义工厂中由于有大量的感应电动机、电焊机、电弧炉及气体放电灯等感性负荷,还有感性的电力变压器,从而使功率因数降低。如在充分发挥设备潜力、改善设备运行性能、提高其自然功率因数的情况下,尚达不到规定的工厂功率因数要求。为了保证供电质量和节能,充分利用电力系统中发配电
27、设备的容量,减小供电线路的截面,减小电网的功率损耗、电能损耗,减小线路的电压损失,必须提高用电单位的功率因数,则需考虑增设无功功率补偿装置。2.1.2补偿装置的确定无功补偿装置包括系统中的并联电容器,串联电容器,并联电抗器,同步调相机和静止无功补偿装置等。其中并联电容器补偿装置时无功负荷的主要电源之一。它具有投资省,装设地点不受自然条件限制,运行简便可靠等优点。故一般首先考虑装设并联电容器。由于它没有旋转部件,维护较为方便,为了在运行中调节电容器的功率,可将电容器连接成若干组,根据负荷变化,分组投入或切除。本次设计为10kV,从补偿装置的维护和性能的角度来考虑,就选用并联电容器装置。2.2无功
28、补偿容量计算 图1-1 无功补偿向量图图1-1率因数提高与无功功率和视在功率变化的关系。假设功率因数有提高到,这时在用户需用的有功功率不变的条件下,无功功率将由减小到,视在功率将由减小到。相应地负荷电流也得以减小,这将使系统的电能损耗和电压损耗相应降低,既节约了电能,又提高了电压质量,而且可选较小容量的供电设备和导线电缆,因此提高功率因数对供电系统大有好处。由图可知,要使功率因数由提高到,必须装设无功补偿装置(并联电容器),其容量为: (1-15)在确定了总的补偿容量后,即可根据所选并联电容器的单个容量来确定电容器的个数,即: (1-16)变电所高压侧的,取。需在低压侧并联电容器的容量为: 根
29、据各种数据,我选定并联电容器的型号为:BWF10.5-30-1 所以 个数应该是3的倍数,所以在低压侧需联27个型号为BWF10.5-30-1的电容器。 说明实际中并联电容器的容量为: 表1-2 无功补偿对照表项目(kW)(kvar)(kW)(A)10KV补偿前负荷0.771960.4841648.582561.51147.810KV侧无功补偿容量-81010KV侧补偿后容量0.911960.484838.582132.1123.1第3章 变电站主接线的设计3.1 主接线的基本要求主接线的选择,要达到安全、可靠、灵活、经济的要求。要在满足供电可靠性的情况下,尽量节省投资。安全:要求选择合适的电
30、气设备,具有良好的监视和保护系统,以保证人身和设备安全。可靠:满足各级负荷的不中断供电要求。灵活:利用较少的切换来适应不同的运行方式,检修方便,电源和负荷投切方便。经济:保证供电可靠性的情况下,尽量节省初投资和年运行费用。此外,变电所扩建的可能性较大,其主接线应该方便改造和扩建。3.2 主接线的选择3.2.1 单母线接线方式单母线也称汇流排,即汇集和分配电能的硬导线。设置母线可以方便地 图3-1 单母线接线 图3-2 单母线分段接线把电源进线和多路引出线通过开关电器连接在一起,以保证供电的可靠性和灵活性。 在主接线中,断路器是电力系统的主开关;隔离开关的功能主要是隔离高压电源,以保证其它设备和
31、线路的安全检修。例如,固定式开关柜中的断路器工作一段时间需要检修时,在断路器断开电路的情况下,拉开隔离开关;恢复供电时,应先合隔离开关,然后合断路器。这就是隔离开关与断路器配合操作的原则。由于隔离开关无灭弧装置,断流能力差,所以不能带负荷操作。如图3-1所示。3.2.2 单母线分段单母线分段接线是采用断路器(或隔离开关)将母线分段,通常是分成两段,如图3-2所示。母线分段后可进行分段检修,对于重要用户,可以从不同段引出两个回路,当一段母线发生故障时,由于分段断路器QF1在继电保护作用下自动将故障段迅速切除,从而保证了正常母线段不间断供电和不致使重要用户停电。两段母线同时故障的几率很小,可以不予
32、考虑。在供电可靠性要求不高时,亦可用隔离开关分段(QS1),任一段母线发生故障时,将造成两段母线同时停电,在判断故障后,拉开分段隔离开关QS1,完好段即可恢复供电。由上可知,单母线分段便于分段检修母线减小母线故障影响范围,提高供电的可靠性和灵活性。电气主接线详见附录1。洛阳理工学院毕业设计(论文)第4章 电源进线及工厂高压配电线路的设计4.1 变电所进出线及与邻近单位联络线的选择4.1.1 10kV高压进线的选择校验采用LJ型铝绞线架空敷设,接往10kV公用干线。(1)按发热条件选择 由查表初选LJ-50,其35C时的满足发热条件。(2)校验机械强度 查表得最小允许截面,因此按发热条件的LJ-
33、50满足机械强度要求。4.1.2 由高压配电室至主变的一段引入电缆的选择校验 采用YJL22-10000型交联聚乙烯绝缘的铝芯电缆直接埋地敷设。(1)按发热条件选择 由及土壤温度得初选截面为的交联电缆,其167.3A,满足发热条件。(2)校验短路热稳定 按式计算满足短路热稳定的最小截面 A=25C值由表查得,按终端变电所保护动作时间0.5s,加断路器短路时间0.2s,再加0.05s计,故。因此YJL22-10000-325电缆满足短路热稳定条件。高压配电线如图4-1所示。图4-1 高压配电图4.1.3 作为备用电源的高压联络线的选择校验 采用YJL22-10000型交联聚乙烯绝缘的铝芯电缆,直
34、接埋地敷设,与相距2km的邻近单位变电所的10kv母线相联。(1)按发热条件选择工厂二级负荷容量共821.15kVA,而最热月土壤平均温度为25C,一次查表,初选缆芯截面为的交联聚乙烯绝缘铝芯电缆(该型电缆最小芯线截面积为),其,满足发热条件。(2)校验电压损耗 由查表可得缆芯为铝芯电缆的(缆芯温度按80C计),而二级负荷的,线路长度按2km计,因此 (3)短路热稳定校验 由前述引入电缆的短路热稳定性校验,可知缆芯的交联电缆是满足短路热稳定要求的。4.2 0.4kV低压出线的选择馈电给各车间(锻工车间、纺纱车间、制条车间、软水站、机修车间、职工车间、染工车间、锅炉房、水泵房、油泵房、化验区)用
35、VLV22型聚氯乙烯绝缘铝芯电缆。馈电给仓库用BLV铝芯聚氯乙烯绝缘导线。馈电给生活区、食堂办公楼用BLX铝芯橡皮绝缘导线。38 第5章 短路计算5.1 短路电流计算的目的短路电流计算的目的是为了正确选择和校验电气设备。进行短路电流计算,首先要绘制计算电路图。在计算电路图上,将短路计算所考虑的各元件的额定参数都表示出来,并将各元件依次编号,然后确定短路计算点。短路计算点要选择得使需要进行短路校验的电气元件有最大可能的短路电流通过。接着,按所选择的短路计算点绘出等效电路图,并计算电路中各主要元件的阻抗。在等效电路图上,只需将被计算的短路电流所流经的一些主要元件表示出来,并标明其序号和阻抗值,然后
36、将等效电路化简。对于工厂供电系统来说,由于将电力系统当作无限大容量电源,而且短路电路也比较简单,因此一般只需采用阻抗串、并联的方法即可将电路化简,求出其等效总阻抗。最后计算短路电流和短路容量。短路电流计算的方法,常用的有欧姆法(有称有名单位制法)和标幺制法(又称相对单位制法)。5.2 短路电流计算的方法 图5-1 系统等效电路图5.2.1 短路计算设,即高压侧,低压侧,则 5.2.2 计算短路电路中各元件的电抗标幺值(1)电力系统,故 (2)架空线路 由资料得LGJ-150的,而线路长,故 (3)电力变压器 计算公式为:查表得变压器T1 ,变压器T2 4,变压器T3,变压器T4 ,变压器T5
37、因此绘短路计算等效电路如图5-2 图5-2 等效阻抗图5.2.3 K-1点短路计算计算k-1点(10.5kV侧)的短路电路总电抗及三相短路电流和短路容量(1)总电抗标幺值 (2)三相短路电流周期分量有效值 (3)其他短路电流 (4)三相短路容量: 5.2.4 K-2点短路计算求K-2点(0.4kV)的短路电路和总电抗及三相短路电流和短路容量(1)总电抗标幺值 (2)三相短路电流周期分量有效值 (3)其他短路电流 (4)三相短路容量: 5.2.5 K-3点短路计算求K-3点(0.4kV)的短路电路和总电抗及三相短路电流和短路容量 (1)总电抗标幺值 (2)三相短路电流周期分量有效值 (3)其他短
38、路电流 (4)三相短路容量: 5.2.6 K-4点短路计算求K-4点(0.4kV)的短路电路和总电抗及三相短路电流和短路容量(1)总电抗标幺值 (2)三相短路电流周期分量有效值 (3)其他短路电流 (4)三相短路容量: 5.2.7 K-5点短路计算求K-5点(0.4kV)的短路电路和总电抗及三相短路电流和短路容量(1)总电抗标幺值 (2)三相短路电流周期分量有效值 (3)其他短路电流 (4)三相短路容量: 5.2.8 K-6点短路计算K-6点(0.4kV)的短路电路和总电抗及三相短路电流和短路容量(1)总电抗标幺值 (2)三相短路电流周期分量有效值 (3)其他短路电流 (4)三相短路容量: 通过计算得表5-1表5-1短路点数据统计表三相短路电流/KA三相短路容量(MVA)短路计算点1.961.961.965.02.9635.719.719.719.736.221.513.77.667.667.6614.18.355.3222.522.522.541.424.5315.6311.2511.2511.2520.712.267.817.667.667.661